Free sample · ElectricianQ1 / 30
Circuit breakers and switches containing fuses shall be located so that they may be operated from a readily accessible place. They shall be installed such that the center of the grip of the operating handle of the switch or circuit breaker, when in its highest position, is not more than <code>________</code> above the floor or working platform.
Correct — D. 240.24. The maximum height above the floor or the working platform that a switch or circuit breaker is allowed to be installed is 6 feet 7 inches.<br/><br/>This is measured from the center of the grip of the operating handle when in its highest position.
↑ Tap an answer to check it
Practice all 30 questions

Heads up: the app and the web exam use separate accounts — a web unlock and an in-app purchase do not carry over. Buy on the web to practice on the web.

Free practice

30 free Electrician questions

Sampled across every topic area — not just the first page. Try them as a quiz or flip them as flashcards.

↓ PDF
  1. Electrician

    Circuit breakers and switches containing fuses shall be located so that they may be operated from a readily accessible place. They shall be installed such that the center of the grip of the operating handle of the switch or circuit breaker, when in its highest position, is not more than <code>________</code> above the floor or working platform.

    Correct — D. 240.24. The maximum height above the floor or the working platform that a switch or circuit breaker is allowed to be installed is 6 feet 7 inches.<br/><br/>This is measured from the center of the grip of the operating handle when in its highest position.
  2. Electrician

    All 125-volt, single-phase receptacles not exceeding 30 amperes located at least within <code>________</code> measured horizontally of the inside wall of a hydromassage tub shall be protected by a ground-fault circuit interrupter.

    Correct — B. The intent of this rule, addressed in Section 680.71, is to prevent a shock hazard in the area surrounding a hydromassage tub that may have the presence of water. <br/><br/>Therefore, all 125-volt, single-phase receptacles of not more than 30 amperes and located within 6 ft. of the tub are to be GFCI protected.
  3. Electrician

    The NEC mandates specific branch circuits, receptacle outlets and utilization equipment to be provided with a ground-fault circuit interrupter (GFCI); this device is intended <code>________</code>.

    Correct — D. Article 100, where definitions are found, reveals a ground-fault circuit interrupter is a device intended for the protection of personnel that functions to de-energize a circuit when a ground-fault occurs.
  4. Electrician

    Circuit breakers used as switches in high-intensity discharge lighting circuits shall be listed and shall be marked as:

    Correct — B. Please Refer: NEC Code 240.83(D).
  5. Electrician

    Where an ac transformer arc welder has a 50-ampere rated primary current and a 60 percent duty cycle, determine the minimum size copper 60 deg. C rated conductors required to supply this welder.

    Correct — C. The loads on transformer arc welders are considered intermittent. <br/><br/>Therefore, the minimum ampacity of the branch-circuit conductors is permitted to be determined by applying the percentage values shown in Table 630.11(A). This calculation is done by selecting the appropriate factor from the table, based on the duty cycle and type of welder, then multiply by the value of the welder rated primary current. The conductors are to be selected from Table 310.16.<br/><br/>.78 (duty cycle factor) x 50 amperes (primary current) = 39 amperes<br/><br/>Table 310.16 requires size 8 AWG 60°C rated conductors.
  6. Electrician

    Which of the following listed conductor insulations is oil resistant?

    Correct — C. Table 310.4(1) shows conductors with MTW insulation to be oil resistant.
  7. Electrician

    When a 2-wire circuit is derived from two ungrounded conductors of a multiwire circuit and is used with switched lampholders, the switching device required is to be:

    Correct — D. Please Refer: NEC Code 410.93.
  8. Electrician

    Determine the voltage drop on a branch circuit given the following related information:<br/><ul><li>current = 5 amperes</li><li>conductor length = 300 ft.</li><li>conductor resistance = 4 ohms per 1,000 feet</li></ul>

    Correct — D. To determine the voltage drop on this circuit, first find the resistance total with the information given in the question:<br/><br/>Resistance = 4 ohms ÷ 1000 ft. = .004 ohms per ft.<br/><br/>.004 ohms x 300 ft. = 1.2 ohms total resistance<br/><br/>Next, apply the voltage drop formula, VD = I X R:<br/><br/>VD= 5 amperes x 1.2 ohms = 6 volts dropped.
  9. Electrician

    The maximum approved electrical trade size for LFNC is <code>________</code>:

    Correct — B. Please Refer: NEC Code 356.20(B).
  10. Electrician

    The branch-circuit conductors supplying fixed electric space-heating equipment and any associated motors shall be sized not smaller than <code>________</code> of the load.

    Correct — A. Fixed electric space-heating equipment is covered in Article 424. <br/><br/>Section 424.4(B) specifically requires branch-circuit conductors for fixed electric space-heating equipment and any associated motors to be sized not smaller than 125% of the load. <br/><br/>This mandate is necessary to protect conductors and overcurrent devices, particularly those in panelboards and load centers, from overheating during periods of prolonged operation.
  11. Electrician

    The ampacity of conductors that connect a capacitor to the terminals of a motor or to motor circuit conductors shall not be less than<code>________</code> the ampacity of the motor circuit conductors and not less than <code>________</code> % of the rated current of capacitors

    Correct — C. Please Refer: NEC Code 460.8.
  12. Electrician

    Which of these fixture wires may be used in an operating temperature of 180°C?

    Correct — D. NEC Table 402.3 specifies maximum operating temperatures for fixture wire materials. SF-1 is usable to 200°C. TFFN is usable up to 90°C. HFF and PGFF are usable up to 150°C.
  13. Electrician

    Splices and taps are permitted in a metal wireway provided they are accessible and do not fill the wireway to more than <code>________</code> of its area at that point.

    Correct — C. As per Section 376.56, splices and taps are permitted within a wireway, provided they are accessible. The splices and taps shall not fill the wireway to more than 75 percent at that point. Conductors in wireways can be accessed through hinged or removable covers.
  14. Electrician

    Where track lighting is installed in a continuous row, each individual section of not more than <code>________</code> in length shall be securely supported.

    Correct — C. As per Section 410.154, where lighting track is installed in a continuous row, each section must be supported at least every 4 ft. to adequately support the lighting track and the weight of the luminaires that can be installed.
  15. Electrician

    An enclosure for an overcurrent device is 8 inches wide and 5 inches deep. The maximum allowable wiring space for conductors, splices, and taps at any cross-section of the enclosure is <code>________</code>.

    Correct — D. NEC 312.8 discusses wiring space within switch and overcurrent device enclosures. 312.8(A) says that the area for conductors, splices, and taps at any cross-section can be no more than 75% of the cross-sectional area of an enclosure for overcurrent devices. This translates to 75% of (8 × 5) = 0.75 × 40 = 30 in<sup>2</sup>. <br/><br/>Choice A represents 40% of the cross-sectional area. <br/><br/>Choice B represents 50%. <br/><br/>Choice D represents 90%.
  16. Electrician

    Unless specifically identified for a higher percentage of fill, the cross-sectional area of the conductors or optical fiber tubes in a conduit seal, in Class I, Divisions 1 and 2 locations, shall not exceed <code>________</code> of the cross-sectional area of a rigid metal conduit (RMC) of the same trade size.

    Correct — D. The intent of Section 501.15(C)(6) is to minimize the passage of gases from one portion of the electrical system to another and to ensure an adequate area is available for pouring the sealing compound. As per Table 1, Chapter 9, the maximum permitted fill area for conduit is 40%; the maximum fill area permitted for standard conduit seals is 25%. If the conduit fill exceeds 25% of the cross-sectional area of the sealing fitting, a larger trade size sealing fitting is required.
  17. Electrician

    Conduit or tubing nipples not over 24 inches in length may be filled to a maximum of <code>________</code> of their cross-sectional area.

    Correct — C. Chapter 9, Informational Note Number 4 to the tables allows a permitted conduit or tubing fill of 60% of their cross-sectional area where the conduit or tubing is not more than 24 inches in length. This is permitted because short sections of the raceways readily permit easy pulling of the conductors and abrasion will not likely occur.
  18. Electrician

    When conductors are installed in a conduit or tubing nipple of <code>________</code> or less in length, the ampacity adjustment factors for more than three (3) current-carrying conductors in the raceway are not required to be applied.

    Correct — D. Section 310.15(C)(1)(b) clarifies that adjustment factors for more than three (3) current-carrying conductors in raceways shall not apply where the raceway is not more than 24 inches in length. <br/><br/>Where more than 3 current-carrying conductors are installed in short lengths of conduit or tubing, the heating effect caused from the additional conductors is insignificant. <br/><br/>Therefore, the ampacity of the conductors is not greatly reduced.
  19. Electrician

    At buildings where communications systems are likely to be used, an intersystem bonding termination shall be provided for the communications systems at an accessible location at the service equipment.<br/><br/>It shall be an aluminum or copper busbar not less than ¼ in. thick x 2 in. wide and be of sufficient length to accommodate not less than <code>________</code> terminations for communications systems in addition to other connections.

    Correct — D. According to Article 100 - Definitions, an intersystem bonding termination is a dedicated location that provides a means to connect communications systems (telephone cable, coaxial cable, satellite dishes, and antennas) to the building grounding electrode system.<br/><br/>The intersystem bonding termination device minimizes damage from induced voltage differences between the systems in the event of lightning occurring or a ground-fault. This bonding termination provides the communications installer an accessible location to bond the systems together without the need to open and work on energized equipment.<br/><br/>Section 250.94(A)(2) tells us that at least three (3) terminations are to be provided for the communications systems.
  20. Electrician

    Recessed or surface-mounted luminaires and recessed exhaust fans may be located within 8 ft from vertically from the top of a bathtub rim:

    Correct — A. Please Refer: NEC Code 410.10(D).
  21. Electrician

    Which of the following is not required to be marked on the nameplate of a transformer?

    Correct — A. The information given on a transformer nameplate is necessary to determine the overcurrent protection, but the overcurrent protection value is not indicated on the nameplate.<br/><br/>Refer to Section 450.11(A).<br/><br/>The overcurrent protection is to be determined in accordance with the values given in Tables 430.3(A) and 430.3(B).
  22. Electrician

    Food waste disposer or dishwasher shall be connected to any of the required 20-ampere small appliance branch circuits in the kitchen.

    Correct — B. Please Refer: NEC Code 210.52(B).
  23. Electrician

    For health care facilities, which of the following branches are not permitted to be arranged for delayed automatic connection to the alternate power source?

    Correct — C. 517.32, 517.35(A). Many equipment branches are required to be automatically connected to an alternate source of power. The branches in 517.35(A) shall be permitted to do so with a delay.<br/><br/>Exit signs must be arranged to have an automatic, non-delayed connection to an alternate source of power. This is most commonly done through an internal battery.
  24. Electrician

    Which term best describes the duty cycle of an appliance that, each hour, is on for 20 minutes at between 30% and 90% load, on for 20 minutes at no load, and off for 20 minutes?

    Correct — D. NEC 100 defines each of the terms listed in the answer choices. <br/><br/>Duty, Periodic is "intermittent operation in which the load conditions are regularly recurrent." Even though the 20-minute load period varies in load, the variation (and the other 40 minutes) are "regularly recurrent." Duty, Short-time (choice B) is a substantially constant load, which does not describe a 30-90% range. <br/><br/>Duty, Continuous (choice C) is when the appliance is at a constant load for an indefinitely long time. <br/><br/>Duty, Varying (choice D) requires both the load and time interval to vary widely; though the load here can vary widely, the time interval does not.
  25. Electrician

    A homeowner wants a new pendant luminaire installed in the ceiling over the middle of a bathtub. The bottom of the luminaire must be at least:

    Correct — A. NEC 410.10(D)(1), which discusses luminaire locations in bathtub and shower areas, requires all parts of a pendant luminaire to be at least 8 feet above the bathtub rim. The 3-foot requirement is for luminaires to be 3 feet horizontally from the top of the bathtub rim.
  26. Electrician

    Which of these generators is allowed to have live parts exposed to accidental contact where accessible to unqualified persons?

    Correct — B. NEC 445 discusses generators, with 445.14 discussing protection of a generator's live parts.<br/><br/>Live parts can be exposed to accidental contact where accessible to unqualified persons if a generator is less than 50 volts ac or 60 volts dc.<br/><br/>Choices A, B, and C are larger than this.
  27. Electrician

    The minimum size of an aluminum TW conductor required for connecting to a 15-hp 500-V DC motor is <code>________</code> AWG.

    Correct — A. NEC Table 430.247 specifies full-load current for DC motors of various horsepowers and armature voltage ratings.<br/><br/>Go down to the row for 15 horsepower and then go across to 500 volts to find the full-load current for this combination as 27 A.<br/><br/>NEC 430.22 requires conductors supplying a single motor in continuous duty to have an ampacity of at least 125% of the motor's full-load current rating, so the conductor must be rated for 27 × 1.25 = 33.8 A.<br/><br/>Now look at Table 310.16 to find the smallest aluminum TW conductor size with an ampacity of at least 33.8 A.<br/><br/>Go down the fourth column for aluminum size TW until you find 35 A, which corresponds to 8 AWG.<br/><br/>The other choices are larger conductor sizes than what is needed.<br/><br/>Ensure that you understand how the tables in this question are used together, as finding the minimum conductor size is a common exam problem.
  28. Electrician

    A driven ground rod or pipe electrode is required to be driven to a depth of at least<code>________</code> into the earth.

    Correct — D. To ensure an adequate grounding system and qualify as an effective grounding electrode, according to Section 250.53(A)(4), all rod and pipe electrodes have at least 8 ft. of length in contact with the soil.
  29. Electrician

    Where a grounding ring consist of size 2 AWG bare copper wire encircling a building, buried 36 inches, in direct contact with the earth, what is the minimum length of the wire permitted for the grounding electrode in this ground ring?

    Correct — A. To qualify as a grounding electrode, the size 2 AWG bare copper conductor is to be in one continuous 20 ft. length. Refer to Section 250.52(A)(4). This type of grounding method is commonly used in sandy areas, such as West Texas, Eastern New Mexico, Arizona, and Southern California.
  30. Electrician

    The minimum cover required for 600 V nominal rated directly buried cable under streets, highways, roads and alleys shall be <code>________</code>:

    Correct — A. Please Refer: NEC Code – Table 300.5.
Sample questions

Electrician sample questions

Tap any question below to reveal the answer and a plain-English explanation.

Electrical Control Devices Disconnecting Circuit breakers and switches containing fuses shall be located so that they may be operated from a readily accessible place. They shall be installed such that the center of the grip of the operating handle of the switch or circuit breaker, when in its highest position, is not more than ________ above the floor or working platform.

A. 6 feet 6 inches

B. 6 feet

C. 7 feet

D. 6 feet 7 inches ✓

Correct — D. 240.24. The maximum height above the floor or the working platform that a switch or circuit breaker is allowed to be installed is 6 feet 7 inches. This is measured from the center of the grip of the operating handle when in its highest position.

Branch Circuit Calculations Conductors Determine the voltage drop on a branch circuit given the following related information: current = 5 amperesconductor length = 300 ft.conductor resistance = 4 ohms per 1,000 feet

A. 0.02 volts

B. 1.2 volts

C. 0.12 volts

D. 6 volts ✓

Correct — D. To determine the voltage drop on this circuit, first find the resistance total with the information given in the question: Resistance = 4 ohms ÷ 1000 ft. = .004 ohms per ft. .004 ohms x 300 ft. = 1.2 ohms total resistance Next, apply the voltage drop formula, VD = I X R: VD= 5 amperes x 1.2 ohms = 6 volts dropped.

Special Occupancies Equipment Conditions At buildings where communications systems are likely to be used, an intersystem bonding termination shall be provided for the communications systems at an accessible location at the service equipment. It shall be an aluminum or copper busbar not less than ¼ in. thick x 2 in. wide and be of sufficient length to accommodate not less than ________ terminations for communications systems in addition to other connections.

A. two

B. five

C. four

D. three ✓

Correct — D. According to Article 100 - Definitions, an intersystem bonding termination is a dedicated location that provides a means to connect communications systems (telephone cable, coaxial cable, satellite dishes, and antennas) to the building grounding electrode system. The intersystem bonding termination device minimizes damage from induced voltage differences between the systems in the event of lightning occurring or a ground-fault. This bonding termination provides the communications installer an accessible location to bond the systems together without the need to open and work on energized equipment. Section 250.94(A)(2) tells us that at least three (3) terminations are to be provided for the communications systems.

What is on the exam

About the Electrician test

Electrician Exam Prep 2026 helps you pass with 483+ realistic practice questions, each with a clear explanation.

Features

  • 483+ practice questions with detailed answer explanations
  • Study modes: quick 10, mock exam, timed, missed questions, and study by topic
  • Progress tracking with subject accuracy and a learning curve
  • Clean, distraction-free design built for focused study

Whether you are just starting or doing a final review before test day, Electrician Exam Prep gives you the questions and explanations you need to build confidence and pass.

You will be tested on

  • Core formulas and field calculations
  • Codes, standards and compliance
  • Safe work practices and PPE
  • Tools, materials and on-site reference

How TheoryPractice helps you pass

  • Real exam-style questions with instant, detailed explanations
  • Full timed mock exams that mirror the real test format
  • Flashcards & quiz modes from the same question bank
  • Progress tracking so you know exactly when you're ready
Coverage

Topics in this question bank

Topic

Core formulas and field calculations

Topic

Codes, standards and compliance

Topic

Safe work practices and PPE

Topic

Tools, materials and on-site reference

Unlock everything

Full Electrician bank + unlimited mocks

Try 30 questions free. Unlock the complete Electrician question bank, every explanation, and unlimited timed mock exams. Practice on any device.

Unlock Electrician →
Cramming?
$2.99
/ week · per exam
Best value
$6.99
/ month · per exam
Questions

Electrician test FAQ

Is the Electrician hard?
The Electrician is very passable when you study with realistic practice questions. Most people only find it tricky because the wording is unfamiliar. Practise in the real question format until you score consistently above the pass mark and you'll walk in confident.
How many questions are on the Electrician?
The exact number depends on the version of the Electrician you sit. Electrician Exam 2026 Prep includes a large bank of practice questions covering every topic, plus full-length mock exams set up to mirror the real test format and pass mark.
Can I practise the Electrician for free?
Yes. You can practise a free sample of Electrician questions on TheoryPractice in your browser, with answers and explanations. A web unlock adds the full question bank and unlimited timed mock exams for this exam.
Does Electrician Exam 2026 Prep work offline?
The web practice works in your browser. If you prefer offline study, use the downloadable PDF or the mobile app where available, then return to the web version for timed mock exams and progress tracking.
Is Electrician practice available in other languages?
Several of our apps support more than one language. Open the Electrician Exam 2026 Prep listing on the App Store or Google Play to see the exact languages available for the Electrician.
How many Electrician questions are there?
This bank covers 30 Electrician practice questions, each with a plain-English explanation for the correct answer.
Is Electrician practice free?
Yes — the sample questions on this page are free to practice. Unlock the full bank and timed mock exams when you're ready to go further.
Where can I practice the Electrician online?
Right here on TheoryPractice, in your browser — no download required.