  1. Q11When inspecting a solar storage tank with an integral heat exchanger, what must be verified regarding the potable water connections?

    • AThat the connections are labeled in multiple languages
    • BThat there is a test point to verify no cross-connection with heat transfer fluid
    • CThat the connections are made of copper only
    • DThat the connections are at least 12 inches apart
    Show answer

    ✓ Correct answer: B. That there is a test point to verify no cross-connection with heat transfer fluid

    A cross-connection test point allows verification that there is no leakage from the heat transfer fluid circuit into the potable water circuit, which could contaminate drinking water.

  2. Q12What type of valve must be installed on the cold water supply line to a solar storage tank?

    • ACheck valve
    • BBall valve
    • CGate valve
    • DNeedle valve
    Show answer

    ✓ Correct answer: A. Check valve

    A check valve prevents thermosiphoning or backflow of heated water into the cold water supply, which could waste energy and potentially damage components not rated for high temperatures.

  3. Q13When inspecting the pressure relief valve on a solar storage tank, what is the most important factor to verify?

    • AThat it is made by the same manufacturer as the tank
    • BThat it was installed within the last year
    • CThat it is connected to the building's drainage system
    • DThat its pressure rating does not exceed the maximum working pressure of the tank
    Show answer

    ✓ Correct answer: D. That its pressure rating does not exceed the maximum working pressure of the tank

    The pressure relief valve must have a pressure rating that does not exceed the maximum working pressure of the tank to ensure it will release pressure before the tank could be damaged.

  4. Q14What must an inspector verify about drain valves on a solar water heating storage tank?

    • AThat they are connected to the building automation system
    • BThat they have lockable handles
    • CThat they are accessible for maintenance and service
    • DThat they are electronically controlled
    Show answer

    ✓ Correct answer: C. That they are accessible for maintenance and service

    Drain valves must be accessible for maintenance and service to allow draining of the tank when necessary, which is a basic requirement for proper system maintenance.

  5. Q15In a solar water heating system, what should be verified about the potable water piping material?

    • AThat it is at least Schedule 80 thickness
    • BThat it is approved for potable water use and rated for the maximum system temperature
    • CThat it matches the color of the solar collectors
    • DThat it is all made from the same manufacturer
    Show answer

    ✓ Correct answer: B. That it is approved for potable water use and rated for the maximum system temperature

    Piping materials must be approved for potable water use and rated for the maximum temperatures that will be experienced in the system to ensure safety and code compliance.

  6. Q16According to plumbing codes, what is required for a heat exchanger that separates potable water from a toxic heat transfer fluid in a solar heating system?

    • ADouble-wall construction with a visible leak path
    • BAnnual pressure testing
    • CElectronic leak detection system
    • DASME certification only
    Show answer

    ✓ Correct answer: A. Double-wall construction with a visible leak path

    Double-wall construction with a visible leak path between the walls is required by plumbing codes to ensure that any leak of toxic heat transfer fluid will be detected before it can contaminate the potable water.

  7. Q17When inspecting a solar water heating system with multiple storage tanks, what must be verified about the piping configuration?

    • AThat all tanks are the same color
    • BThat tanks are arranged in increasing size order
    • CThat each tank has a separate pressure gauge
    • DThat balancing valves are installed to ensure equal flow through all tanks
    Show answer

    ✓ Correct answer: D. That balancing valves are installed to ensure equal flow through all tanks

    Proper balancing valves are required to ensure equal flow through multiple tanks, which prevents short-circuiting and ensures all tanks contribute to the system's performance.

  8. Q18What should an inspector verify about the circulator pump in the potable water loop of a solar water heating system?

    • AThat it is made by the same manufacturer as the collectors
    • BThat it is manually controlled
    • CThat it is approved for use in potable water systems
    • DThat it runs continuously
    Show answer

    ✓ Correct answer: C. That it is approved for use in potable water systems

    Pumps in potable water systems must be specifically approved for potable water use to prevent contamination from materials not suitable for drinking water.

  9. Q19When inspecting a solar water heating system's storage tank, what is required regarding insulation?

    • AThat the insulation is made by the same manufacturer as the tank
    • BThat it has proper insulation that meets code requirements for R-value
    • CThat the insulation is the same color as the tank
    • DThat the insulation is at least 1 inch thick regardless of type
    Show answer

    ✓ Correct answer: B. That it has proper insulation that meets code requirements for R-value

    Storage tanks must be properly insulated to minimize heat loss, with insulation materials meeting code requirements for R-value and fire resistance.

  10. Q20During inspection of a solar water heating system, what must be verified about the temperature sensor wells on the storage tank?

    • AThat they are properly sealed to prevent leakage
    • BThat they are located on the north side of the tank
    • CThat they are connected to the building's fire alarm system
    • DThat they are made of plastic materials
    Show answer

    ✓ Correct answer: A. That they are properly sealed to prevent leakage

    Temperature sensor wells must be properly sealed to prevent water leakage while allowing accurate temperature measurement for system control.