HomeHome Inspector Exam PrepQuestions 1–10
Home InspectorPart 1 of 3

Home Inspector Exam Questions & Answers 2026 (1–10)

Home Inspector practice questions and answers 2026. Tap an option to test yourself — you'll see the correct answer and a plain-English explanation for every question. Free, no login.

Practise Home Inspector questions free, download the PDF, or unlock timed mock exams when you are ready.
Download PDFWatch video
Multiple choice — pick the best answer, then reveal it
  1. Q1What is the minimum clearance required between the service drop conductors and the roof surface over which they pass (where the roof pitch is less than 4 in 12)?

    • A8 feet
    • B3 feet
    • C10 feet
    • D18 inches
    Show answer

    ✓ Correct answer: A. 8 feet

    NEC 230.24 requires at least 8 feet of clearance above a roof surface for service conductors where the pitch is less than 4/12. Steeper pitches allow a reduced 3-foot clearance.

    Topic: Electrical Systems

  2. Q2The weatherhead (service entrance head) for overhead service conductors must be located at or above which point relative to the service equipment?

    • AAt the electric meter
    • BAt the main breaker
    • CAbove the service-entrance cable connection to the service drop
    • DAt grade level
    Show answer

    ✓ Correct answer: C. Above the service-entrance cable connection to the service drop

    The weatherhead must be positioned at the top of the service entrance so that the drip loop directs water away and the conductors enter from above, preventing water infiltration.

    Topic: Electrical Systems

  3. Q3A residential service entrance conductor must maintain a minimum clearance above a public sidewalk or walkway of:

    • A8 feet
    • B10 feet
    • C12 feet
    • D15 feet
    Show answer

    ✓ Correct answer: B. 10 feet

    NEC 230.24(B) requires service conductors to maintain at least 10 feet of clearance above walkways accessible only to pedestrians, ensuring pedestrian safety beneath the wires.

    Topic: Electrical Systems

  4. Q4When inspecting a service entrance, a home inspector finds that the service entrance cable is stapled directly to the wood framing inside the wall cavity without protection. This is a concern because:

    • AIt increases voltage drop
    • BIt voids the meter warranty
    • CIt reduces ampacity below rating
    • DPhysical damage to the cable could cause a fire or shock hazard
    Show answer

    ✓ Correct answer: D. Physical damage to the cable could cause a fire or shock hazard

    Service entrance cable in accessible locations must be protected from physical damage. Unprotected cable is subject to nail punctures and abrasion, which can compromise the insulation and create hazards.

    Topic: Electrical Systems

  5. Q5A 200-amp residential service requires copper service entrance conductors of at least which AWG size?

    • A2/0 AWG
    • B1/0 AWG
    • C4/0 AWG
    • D2 AWG
    Show answer

    ✓ Correct answer: A. 2/0 AWG

    NEC Table 310.12 permits 2/0 AWG copper conductors for a 200-amp residential service. Aluminum would require 4/0 AWG for the same rating, reflecting aluminum's lower conductivity.

    Topic: Electrical Systems

  6. Q6What is the primary purpose of a grounding electrode system at a residence?

    • ATo provide a return path for normal current flow
    • BTo limit voltage imposed on the system from lightning and utility line surges
    • CTo increase the ampacity of branch circuits
    • DTo detect ground fault currents
    Show answer

    ✓ Correct answer: B. To limit voltage imposed on the system from lightning and utility line surges

    The grounding electrode system connects the electrical system to earth to stabilize system voltage and provide a path to dissipate lightning and utility surge energy, protecting equipment and occupants.

    Topic: Electrical Systems

  7. Q7Which of the following is a recognized grounding electrode under the NEC?

    • AThe neutral conductor of the service
    • BA plastic water pipe buried in the ground
    • CA concrete-encased electrode (Ufer ground)
    • DAn aluminum rod driven 8 feet into the earth
    Show answer

    ✓ Correct answer: C. A concrete-encased electrode (Ufer ground)

    A concrete-encased electrode (Ufer ground) — 20 feet or more of rebar in a concrete foundation — is a recognized NEC grounding electrode. Aluminum rods are not permitted, and plastic pipe is not conductive.

    Topic: Electrical Systems

  8. Q8Bonding of metal gas piping to the electrical system is required because:

    • AIt improves appliance efficiency
    • BIt reduces static electricity
    • CIt keeps gas piping from corroding
    • DIt prevents dangerous voltage differences that could ignite gas
    Show answer

    ✓ Correct answer: D. It prevents dangerous voltage differences that could ignite gas

    Metal gas piping that is not bonded to the electrical system can accumulate a voltage potential. Bonding equalizes potential and prevents arcing near gas piping, which could ignite leaking gas.

    Topic: Electrical Systems

  9. Q9A ground rod used as a grounding electrode must be driven to a minimum depth of:

    • A8 feet
    • B4 feet
    • C6 feet
    • D10 feet
    Show answer

    ✓ Correct answer: A. 8 feet

    NEC 250.52(A)(5) requires driven ground rods to be installed to a minimum depth of 8 feet to ensure adequate soil contact and effective grounding.

    Topic: Electrical Systems

  10. Q10At a service panel, the neutral bar and the equipment grounding bar must be bonded together. In a subpanel fed from the main panel, this bonding strap should be:

    • AConnected to both the neutral and ground bars
    • BRemoved so that neutrals and grounds remain separate
    • CConnected only to the ground bar
    • DDoubled to carry the full load current
    Show answer

    ✓ Correct answer: B. Removed so that neutrals and grounds remain separate

    In a subpanel (remote distribution panel), the neutral must be kept isolated from the equipment grounding conductors. The main panel is the only place where the neutral-to-ground bond is made, preventing parallel neutral current paths through the grounding system.

    Topic: Electrical Systems

Free practice here. Timed mocks when you are ready.

Use the free Home Inspector Exam Prep sample, download the PDF, then unlock web-based timed mock exams for a full exam rehearsal.

Download PDFStart practice test