  1. Q1What is the primary purpose of a supply duct in an HVAC system?

    • ADeliver conditioned air from the air handler to the occupied space
    • BReturn room air back to the air handler for reconditioning
    • CExhaust stale air to the outdoors
    • DProvide fresh outdoor makeup air to the system
    Show answer

    ✓ Correct answer: A. Deliver conditioned air from the air handler to the occupied space

    Supply ducts carry conditioned (heated or cooled) air from the air-handling unit to registers in the occupied space. Return ducts perform the reverse function, pulling room air back to be reconditioned.

    Topic: Airflow & Ductwork

  2. Q2Which unit is used to express airflow volume in HVAC ductwork?

    • APounds per square inch (PSI)
    • BFeet per minute (FPM)
    • CCubic feet per minute (CFM)
    • DInches of water column (in. w.c.)
    Show answer

    ✓ Correct answer: C. Cubic feet per minute (CFM)

    Airflow volume is measured in cubic feet per minute (CFM). FPM measures velocity, and in. w.c. measures static pressure — both related but distinct from volume.

    Topic: Airflow & Ductwork

  3. Q3What does 'static pressure' represent in a duct system?

    • AThe velocity of air moving through the duct
    • BThe pressure exerted equally in all directions on the duct walls
    • CThe total volume of air in the duct at a given moment
    • DThe temperature differential between supply and return air
    Show answer

    ✓ Correct answer: B. The pressure exerted equally in all directions on the duct walls

    Static pressure acts outward in all directions on duct walls and is what drives leakage through seams and holes. It is distinct from velocity pressure, which acts only in the direction of airflow.

    Topic: Airflow & Ductwork

  4. Q4Velocity pressure in a duct is best described as:

    • AThe pressure loss caused by duct friction
    • BThe static pressure measured at the fan outlet
    • CThe difference between total pressure and dynamic pressure
    • DThe pressure component due to the kinetic energy of moving air
    Show answer

    ✓ Correct answer: D. The pressure component due to the kinetic energy of moving air

    Velocity pressure (VP) results from the kinetic energy of air in motion. It acts only in the direction of airflow and equals (V/4005)² in. w.c., where V is velocity in FPM at standard air density.

    Topic: Airflow & Ductwork

  5. Q5Total pressure in a duct is the sum of which two pressures?

    • AStatic pressure and velocity pressure
    • BSupply pressure and return pressure
    • CPositive pressure and negative pressure
    • DFan pressure and friction pressure
    Show answer

    ✓ Correct answer: A. Static pressure and velocity pressure

    Total pressure = static pressure + velocity pressure (Bernoulli). Knowing total pressure is essential for understanding how fans and ducts interact at any operating point.

    Topic: Airflow & Ductwork

  6. Q6The basic airflow equation CFM = Area × Velocity requires area in which unit?

    • ASquare inches
    • BSquare feet
    • CSquare meters
    • DLinear feet
    Show answer

    ✓ Correct answer: B. Square feet

    When velocity is in feet per minute (FPM), area must be in square feet to produce CFM directly. Convert square inches to square feet by dividing by 144.

    Topic: Airflow & Ductwork

  7. Q7A 3-ton residential air conditioner requires 400 CFM per ton. What total airflow should the system deliver?

    • A800 CFM
    • B400 CFM
    • C1,200 CFM
    • D1,600 CFM
    Show answer

    ✓ Correct answer: C. 1,200 CFM

    400 CFM/ton × 3 tons = 1,200 CFM. The 400 CFM/ton rule of thumb is a standard residential design target ensuring adequate sensible heat removal and coil performance.

    Topic: Airflow & Ductwork

  8. Q8Room-by-room CFM requirements are determined during which ACCA design procedure?

    • AManual N (commercial load calculation)
    • BManual S (equipment selection)
    • CManual D (duct design)
    • DManual J (residential load calculation)
    Show answer

    ✓ Correct answer: D. Manual J (residential load calculation)

    ACCA Manual J calculates room-by-room heating and cooling loads, which are converted to CFM requirements. Manual D uses those CFM values to size ducts; Manual S selects the equipment.

    Topic: Airflow & Ductwork

  9. Q9A supply plenum feeds three branch ducts carrying 300, 450, and 250 CFM respectively. The main trunk must carry at least how much CFM?

    • A1,000 CFM
    • B450 CFM
    • C750 CFM
    • D900 CFM
    Show answer

    ✓ Correct answer: A. 1,000 CFM

    The main trunk must carry the sum of all branches: 300 + 450 + 250 = 1,000 CFM. Conservation of mass (continuity equation) requires airflow entering a junction to equal airflow leaving.

    Topic: Airflow & Ductwork

  10. Q10A space has a sensible cooling load of 10,800 BTU/h with a supply-air temperature of 55°F and a room design temperature of 75°F. What supply airflow is required?

    • A450 CFM
    • B500 CFM
    • C600 CFM
    • D675 CFM
    Show answer

    ✓ Correct answer: B. 500 CFM

    CFM = Q ÷ (1.08 × ΔT) = 10,800 ÷ (1.08 × 20) = 10,800 ÷ 21.6 = 500 CFM. The constant 1.08 = 0.075 lb/ft³ × 0.24 BTU/(lb·°F) × 60 min/hr, applicable at standard air density.

    Topic: Airflow & Ductwork