  1. Q11A dwelling unit has 2,000 square feet of living area. Using the NEC general lighting load calculation, what is the minimum VA load assigned for general lighting?

    • A4,000 VA
    • B5,000 VA
    • C6,000 VA
    • D8,000 VA
    Show answer

    ✓ Correct answer: C. 6,000 VA

    At 3 VA per square foot (NEC Table 220.12), a 2,000 sq ft dwelling requires 2,000 × 3 = 6,000 VA for general lighting load before applying any demand factors.

    Topic: Branch Circuits, Feeders & Services

  2. Q12How many VA is added for each two-wire small-appliance branch circuit when calculating dwelling unit loads?

    • A1,000 VA
    • B1,500 VA
    • C2,000 VA
    • D3,000 VA
    Show answer

    ✓ Correct answer: B. 1,500 VA

    NEC 220.52(A) requires that each 20-ampere small-appliance branch circuit be counted at 1,500 VA when calculating dwelling unit feeder and service loads.

    Topic: Branch Circuits, Feeders & Services

  3. Q13According to NEC Table 220.42, what demand factor applies to the first 3,000 VA of general lighting load for a dwelling unit?

    • A50%
    • B75%
    • C35%
    • D100%
    Show answer

    ✓ Correct answer: D. 100%

    NEC Table 220.42 (formerly Table 220.11) requires that the first 3,000 VA of general lighting load for dwelling units be calculated at 100% demand factor. The remaining load receives reduced demand factors.

    Topic: Branch Circuits, Feeders & Services

  4. Q14For a dwelling unit, NEC Table 220.42 applies what demand factor to general lighting load from 3,001 VA to 120,000 VA?

    • A35%
    • B50%
    • C75%
    • D25%
    Show answer

    ✓ Correct answer: A. 35%

    NEC Table 220.42 specifies that the portion of general lighting load from 3,001 VA to 120,000 VA is calculated at a 35% demand factor, acknowledging that not all loads operate simultaneously.

    Topic: Branch Circuits, Feeders & Services

  5. Q15Feeder conductors must have sufficient ampacity to serve the loads they supply. At minimum, feeder ampacity must not be less than:

    • A100% of the continuous load only
    • B80% of the total connected load
    • C125% of the continuous load plus 100% of the non-continuous load
    • D115% of the total calculated load
    Show answer

    ✓ Correct answer: C. 125% of the continuous load plus 100% of the non-continuous load

    NEC 215.2 requires feeder conductors to have ampacity not less than 125% of the continuous load plus 100% of the non-continuous load, before applying any demand factors.

    Topic: Branch Circuits, Feeders & Services

  6. Q16A feeder supplies a continuous load of 40 amperes and a non-continuous load of 20 amperes. What is the minimum required feeder conductor ampacity?

    • A60 amperes
    • B70 amperes
    • C75 amperes
    • D80 amperes
    Show answer

    ✓ Correct answer: B. 70 amperes

    Continuous load: 40 A × 125% = 50 A; Non-continuous load: 20 A × 100% = 20 A; Total = 70 A minimum. This is per NEC 215.2(A)(1).

    Topic: Branch Circuits, Feeders & Services

  7. Q17What is the minimum service size required for a new single-family dwelling unit according to the NEC?

    • A60 amperes
    • B80 amperes
    • C90 amperes
    • D100 amperes
    Show answer

    ✓ Correct answer: D. 100 amperes

    NEC 230.79(C) requires a minimum 100-ampere, 3-wire service for any single-family dwelling unit. This ensures adequate capacity for modern electrical loads.

    Topic: Branch Circuits, Feeders & Services

  8. Q18Service entrance conductors run above ground outside a building must maintain a minimum clearance of how many feet above finished grade where subject to pedestrian traffic only?

    • A10 feet
    • B12 feet
    • C15 feet
    • D18 feet
    Show answer

    ✓ Correct answer: A. 10 feet

    NEC 230.24(B) requires service conductors above roofs or over pedestrian areas to maintain at least 10 feet above finished grade for areas accessible only to pedestrians.

    Topic: Branch Circuits, Feeders & Services

  9. Q19Overhead service conductors crossing a public street with truck traffic must maintain a minimum vertical clearance of:

    • A12 feet
    • B15 feet
    • C18 feet
    • D20 feet
    Show answer

    ✓ Correct answer: C. 18 feet

    NEC 230.24(B)(4) requires 18 feet of clearance over public streets, alleys, roads, or driveways subject to truck traffic to prevent contact with tall vehicles.

    Topic: Branch Circuits, Feeders & Services

  10. Q20The NEC limits the number of disconnects permitted at the service to a maximum of:

    • AFour disconnects
    • BSix disconnects
    • CEight disconnects
    • DTen disconnects
    Show answer

    ✓ Correct answer: B. Six disconnects

    NEC 230.71(A) permits a maximum of six disconnecting means grouped at one location for a service. This is commonly called the 'rule of six' for service disconnects.

    Topic: Branch Circuits, Feeders & Services