Q11A dwelling unit has 2,000 square feet of living area. Using the NEC general lighting load calculation, what is the minimum VA load assigned for general lighting?
✓ Correct answer: C. 6,000 VA
At 3 VA per square foot (NEC Table 220.12), a 2,000 sq ft dwelling requires 2,000 × 3 = 6,000 VA for general lighting load before applying any demand factors.
Topic: Branch Circuits, Feeders & Services
Q12How many VA is added for each two-wire small-appliance branch circuit when calculating dwelling unit loads?
✓ Correct answer: B. 1,500 VA
NEC 220.52(A) requires that each 20-ampere small-appliance branch circuit be counted at 1,500 VA when calculating dwelling unit feeder and service loads.
Topic: Branch Circuits, Feeders & Services
Q13According to NEC Table 220.42, what demand factor applies to the first 3,000 VA of general lighting load for a dwelling unit?
✓ Correct answer: D. 100%
NEC Table 220.42 (formerly Table 220.11) requires that the first 3,000 VA of general lighting load for dwelling units be calculated at 100% demand factor. The remaining load receives reduced demand factors.
Topic: Branch Circuits, Feeders & Services
Q14For a dwelling unit, NEC Table 220.42 applies what demand factor to general lighting load from 3,001 VA to 120,000 VA?
✓ Correct answer: A. 35%
NEC Table 220.42 specifies that the portion of general lighting load from 3,001 VA to 120,000 VA is calculated at a 35% demand factor, acknowledging that not all loads operate simultaneously.
Topic: Branch Circuits, Feeders & Services
Q15Feeder conductors must have sufficient ampacity to serve the loads they supply. At minimum, feeder ampacity must not be less than:
✓ Correct answer: C. 125% of the continuous load plus 100% of the non-continuous load
NEC 215.2 requires feeder conductors to have ampacity not less than 125% of the continuous load plus 100% of the non-continuous load, before applying any demand factors.
Topic: Branch Circuits, Feeders & Services
Q16A feeder supplies a continuous load of 40 amperes and a non-continuous load of 20 amperes. What is the minimum required feeder conductor ampacity?
✓ Correct answer: B. 70 amperes
Continuous load: 40 A × 125% = 50 A; Non-continuous load: 20 A × 100% = 20 A; Total = 70 A minimum. This is per NEC 215.2(A)(1).
Topic: Branch Circuits, Feeders & Services
Q17What is the minimum service size required for a new single-family dwelling unit according to the NEC?
✓ Correct answer: D. 100 amperes
NEC 230.79(C) requires a minimum 100-ampere, 3-wire service for any single-family dwelling unit. This ensures adequate capacity for modern electrical loads.
Topic: Branch Circuits, Feeders & Services
Q18Service entrance conductors run above ground outside a building must maintain a minimum clearance of how many feet above finished grade where subject to pedestrian traffic only?
✓ Correct answer: A. 10 feet
NEC 230.24(B) requires service conductors above roofs or over pedestrian areas to maintain at least 10 feet above finished grade for areas accessible only to pedestrians.
Topic: Branch Circuits, Feeders & Services
Q19Overhead service conductors crossing a public street with truck traffic must maintain a minimum vertical clearance of:
✓ Correct answer: C. 18 feet
NEC 230.24(B)(4) requires 18 feet of clearance over public streets, alleys, roads, or driveways subject to truck traffic to prevent contact with tall vehicles.
Topic: Branch Circuits, Feeders & Services
Q20The NEC limits the number of disconnects permitted at the service to a maximum of:
✓ Correct answer: B. Six disconnects
NEC 230.71(A) permits a maximum of six disconnecting means grouped at one location for a service. This is commonly called the 'rule of six' for service disconnects.
Topic: Branch Circuits, Feeders & Services