  1. Q21Where must the service disconnecting means be located?

    • AInside the building, within 10 feet of the meter
    • BAt the meter base
    • CAt any accessible location inside the building
    • DAt the nearest point of entrance of the service conductors inside or outside the building
    Show answer

    ✓ Correct answer: D. At the nearest point of entrance of the service conductors inside or outside the building

    NEC 230.70(A)(1) requires the service disconnecting means to be installed at a readily accessible location, either outside the building/structure or inside nearest the point of entry of the service conductors.

    Topic: Branch Circuits, Feeders & Services

  2. Q22Branch circuit conductors must be protected by an overcurrent device at the point where:

    • AThey receive their supply
    • BThey connect to the load
    • CThey pass through a wall
    • DThey change size
    Show answer

    ✓ Correct answer: A. They receive their supply

    Overcurrent protection for branch circuit conductors must be located at the point where the conductors receive their supply (the panelboard or source). This protects the conductors from excessive current.

    Topic: Branch Circuits, Feeders & Services

  3. Q23A single non-motor load is rated as a continuous load. The branch circuit overcurrent device must be rated at no less than:

    • A100% of the load current
    • B110% of the load current
    • C125% of the load current
    • D150% of the load current
    Show answer

    ✓ Correct answer: C. 125% of the load current

    Per NEC 210.20(A), the overcurrent device for a branch circuit supplying a continuous load must have a rating of at least 125% of the continuous load current to prevent nuisance tripping during sustained operation.

    Topic: Branch Circuits, Feeders & Services

  4. Q24Under the 10-foot tap rule, which condition must be met regarding conductor ampacity?

    • AThe tap conductor ampacity must equal the feeder ampacity
    • BThe tap conductor ampacity must be at least 10% of the feeder overcurrent device rating
    • CThe tap conductor ampacity must be at least 1/10 of the overcurrent device rating protecting the feeder
    • DThe tap conductor must be protected by its own overcurrent device at the tap point
    Show answer

    ✓ Correct answer: B. The tap conductor ampacity must be at least 10% of the feeder overcurrent device rating

    NEC 240.21(B)(1) allows a 10-foot tap without overcurrent protection at the tap point if the tap conductor has an ampacity at least 1/10 (10%) of the feeder OCPD rating, the tap is in a raceway, and it terminates in a single OCPD.

    Topic: Branch Circuits, Feeders & Services

  5. Q25The 25-foot feeder tap rule (NEC 240.21(B)(2)) requires that the tap conductors have an ampacity of at least:

    • A25% of the feeder OCPD rating
    • B50% of the feeder OCPD rating
    • C100% of the feeder OCPD rating
    • D1/3 of the feeder OCPD rating
    Show answer

    ✓ Correct answer: D. 1/3 of the feeder OCPD rating

    Under the 25-foot tap rule, the tap conductors must have an ampacity not less than 1/3 of the rating of the overcurrent device protecting the feeder conductors, and they must terminate in a single breaker or set of fuses.

    Topic: Branch Circuits, Feeders & Services

  6. Q26What is the 60°C column ampacity of 10 AWG copper in NEC Table 310.12 for residential branch circuits?

    • A30 amperes
    • B35 amperes
    • C40 amperes
    • D25 amperes
    Show answer

    ✓ Correct answer: A. 30 amperes

    Per NEC Table 310.12, 10 AWG copper conductors have an ampacity of 30 amperes at 60°C, which is the temperature column used for 15- and 20-ampere residential branch circuits when termination temperature is unknown.

    Topic: Branch Circuits, Feeders & Services

  7. Q27When more than three current-carrying conductors are in a raceway, the conductor ampacity must be reduced. What correction factor applies for 4–6 current-carrying conductors in a conduit?

    • A50% of table value
    • B70% of table value
    • C80% of table value
    • D90% of table value
    Show answer

    ✓ Correct answer: C. 80% of table value

    NEC Table 310.15(C)(1) specifies an 80% (0.80) adjustment factor when 4 to 6 current-carrying conductors are bundled in a raceway or cable to account for heat buildup.

    Topic: Branch Circuits, Feeders & Services

  8. Q28GFCI protection for receptacles in bathrooms of dwelling units is required by which NEC article section?

    • ANEC 210.8(B)
    • BNEC 210.8(A)(1)
    • CNEC 210.11(C)
    • DNEC 230.95
    Show answer

    ✓ Correct answer: B. NEC 210.8(A)(1)

    NEC 210.8(A)(1) requires GFCI protection for all 125-volt, single-phase, 15- and 20-ampere receptacles in bathrooms of dwelling units to protect against electric shock in wet locations.

    Topic: Branch Circuits, Feeders & Services

  9. Q29GFCI protection is required for receptacles located outdoors at dwelling units when:

    • AThe receptacle is within 50 feet of a water source
    • BThe receptacle is in an exposed location only
    • CThe receptacle is on a grade-level porch or patio only
    • DAll outdoor receptacles at dwelling units regardless of location
    Show answer

    ✓ Correct answer: D. All outdoor receptacles at dwelling units regardless of location

    NEC 210.8(A)(3) requires GFCI protection for all 125-volt, 15- and 20-ampere receptacles installed outdoors at dwelling units, without restriction to specific outdoor locations.

    Topic: Branch Circuits, Feeders & Services

  10. Q30Ground-fault protection of equipment (GFPE) at the service disconnect is required for solidly grounded wye services of more than 150 volts to ground but not exceeding 600 volts phase-to-phase when the service exceeds:

    • A1,000 amperes
    • B800 amperes
    • C600 amperes
    • D1,200 amperes
    Show answer

    ✓ Correct answer: A. 1,000 amperes

    NEC 230.95 requires GFPE at the service disconnect for solidly grounded wye services over 150V to ground (not exceeding 600V phase-to-phase) where the service exceeds 1,000 amperes. This protects against arcing ground faults.

    Topic: Branch Circuits, Feeders & Services